???jsp.display-item.identifier??? https://repositorio.unipampa.edu.br/jspui/handle/riu/5826
Tipo: Trabalho de Conclusão de Curso
metadata.dc.title: Estudo da eficiência energética de um ar - condicionado com controle automatizado
Autor(es): Silveira , Bruna Fontenele Ferreira
Primeiro Orientador: Silva, Sabrina Neves da
1° Membro da banca: Silva, Sabrina Neves da
2° Membro da banca: Moraes, Marcelo Romero de
3° Membro da banca: Paz, Martín Cruz Rodrigues
Resumo: O uso de equipamentos de ar-condicionado cresce exponencialmente, modifica as características de consumo de energia elétrica e promove impactos relevantes no sistema elétrico mundial, principalmente o brasileiro. Nas Universidades há um significativo aumento por demanda de energia elétrica, que pode levar a 50% de acréscimo no valor da fatura de energia, isso somente no que abrange o uso de aparelhos condicionadores de ar . Ações coordenadas de eficiência energética promovem um conjunto de reduções de insumos, bem como nos custos de manutenção e operação, evita investimentos desnecessário em infraestrutura, além de redução direta do consumo de energia e melhoria na qualidade e confiabilidade dos processos. Os estudos em busca de equipamentos ou alternativas mais eficientes é de suma importância, a fim de não sobrecarregar o sistema, otimizar o consumo de energia elétrica através de instrumentos de medição automatizados. O presente trabalho avalia a eficiência energética de um condicionador de ar, instalado em uma sala da Universidade Federal do Pampa, através de medições do seu consumo energético, obtido com um interruptor inteligente sem fio, e alternando dois materiais isolantes térmicos encaixados no condensador do ar-condicionado, a fim de medir a eficiência desse equipamento em variadas situações, sob a influência da radiação solar. A metodologia consiste em: a) caracterizar o equipamento e local do estudo; b) selecionar materiais de descarte para usar como malha térmica no condensador; c) instalar o interruptor de energia sem fio para monitorar remotamente o comportamento da eletricidade no equipamento; d) definir os critérios de medição, tais como intervalo de tempo, velocidade do ventilador e temperatura do aparelho; e) medir o consumo energético do ar condicionado; f) levantar dados climáticos nos períodos medidos, como temperatura externa e radiação solar; g) tratar os dados climáticos; h) estimar a eficiência energética do sistema proposto e i) avaliar os resultados coletados e comparar com o garantido pelo fabricante do aparelho. As medições demonstraram que há uma influência do revestimento, sobretudo a malha térmica feita com Tetra Pack, pois o consumo diminuiu cerca de 103 kWh, em comparação com a condição sem revestimento. O desenvolvimento do trabalho baseia-se na revisão de literatura, ressalta ideias que envolvem a temática abordada e produz conclusões acerca dos resultados obtidos.
Abstract: The use of air conditioning equipment grows exponentially, modifies the characteristics of electricity consumption, and promotes relevant impacts on the world electric system, especially the Brazilian one. In universities there is a significant increase in energy demand, which can lead to a 50% increase in the value of the energy bill, this only in the use of air conditioners. Coordinated energy efficiency actions promote a set of reductions in the production, as well as maintenance and operation costs, avoid unnecessary investments in infrastructure, in addition to direct reduction of energy consumption and improvement in the quality and reliability of processes. Studies in search of more efficient equipment or alternatives is of paramount importance, in order not to overload the system, optimizing the consumption of electricity through automated measuring instruments. The present work evaluates the energy efficiency of an air conditioner, installed in a room the Federal University of Pampa, through measurements of its energy consumption, obtained with a wireless smart switch, and alternating two thermal insulating materials embedded in the air conditioning condenser, to measure the efficiency of this equipment in various situations, under the influence of solar radiation. The methodology consists of: a) characterizing the equipment and site of the study; b) selecting disposal materials to use as thermal mesh in the condenser; c) installing the wireless power switch to remotely monitor the behavior of electricity in the equipment; (d) define the measurement criteria, such as time interval, fan speed and temperature of the appliance; e) measure the energy consumption of air conditioning; f) collect climate data in the measured periods, such as external temperature and solar radiation; (g) to process climate data; h) estimate the energy efficiency of the proposed system and i) evaluate the results collected and compare with that guaranteed by the manufacturer of the appliance. The measurements showed that there is an influence of the coating, especially the thermal mesh made with Tetra Pack, because the consumption decreased by about 103 kWh, compared to the uncoated condition. The development of the work is based on the literature review, highlights ideas that involve the theme addressed and produces conclusions about the results obtained.
metadata.dc.subject: Eficiência energética
Tetra Pak
Materiais refletores de radiação
Ar- condicionado
Automatização
Energy efficiency
Radiation reflective materials
Air conditioning
Automation
CNPQ: CNPQ::ENGENHARIAS
Idioma: por
metadata.dc.publisher.country: Brasil
metadata.dc.publisher: Universidade Federal do Pampa
Sigla da Instituição: UNIPAMPA
Campus: Campus Bagé
metadata.dc.identifier.citation: SILVEIRA, Bruna Fontenele Ferreira . Estudo da eficiência energética de um ar - condicionado com controle automatizado. 97 p. 2021. Trabalho de Conclusão de Curso (Graduação em Engenharia de Energia) – Universidade Federal do Pampa, Campus Bagé, Bagé, 2021.
Tipo de acesso: Acesso Aberto
metadata.dc.identifier.uri: http://dspace.unipampa.edu.br:8080/jspui/handle/riu/5826
metadata.dc.date.issued: 7-May-2021
???org.dspace.app.webui.jsptag.ItemTag.appears???Engenharia de Energias Renováveis e de Ambiente

???org.dspace.app.webui.jsptag.ItemTag.files???
???org.dspace.app.webui.jsptag.ItemTag.file??? ???org.dspace.app.webui.jsptag.ItemTag.description??? ???org.dspace.app.webui.jsptag.ItemTag.filesize??????org.dspace.app.webui.jsptag.ItemTag.fileformat??? 
TCC_Bruna_Fontene_Fereira_Silveira.pdf3.27 MBAdobe PDF???org.dspace.app.webui.jsptag.ItemTag.view???


???jsp.display-item.copyright???